NOTE:
The Rexroth drive has absolute encoders, therefore a battery is necessary to back-up the encoder signals. If the battery is low you will receive an error message.

 

Exchange the battery, according to the Rexroth manual.

NOTE:
In case the position is lost you need to reset to the reference point, find instructions after the Rexroth manual.

 

ATTENTION:
Do not switch off the machine, if you exchange the battery, otherwise the position gets lost.

NOTE:
The impact of this problem – PLC might switch to stop, and the centering column will lower itself.

 

Check the wiring of the holding magnet for a short circuit.

 

Exchange the relay of the magnet control. Refer to the electrical scheme and picture beside.

Preparing of LAN or WLAN access:

  1. Connect a new PC or laptop with the Wifi of the slitter (CM_POWER_CONTROL). If you don’t have the password, contact Can Man
  2. Open the network setting of that new device and set a fix IP address = 192.168.10.50 SubNet 255.255.255.0
  3. Transfer the “CanMan” folder (C:CanMan) with the programs from the original windows tablet to the new device

How to start panel/HMI software:

  1. Open the folder “CanMan”
  2. Open the folder “Runtime”
  3. Double click the file “WinGRS”
  4. Now the software starts and you can use it to control the slitter

Note: Panel Software is starting in Demo mode and does work for 60min only. After that it has to be restarted. To run the HMI without time limit you need a new license or if the original panel is not in use anymore the license can be transferred with the designated form:


Setting up of a new device in case of an unserviceable device:

  1. Ask Can Man for the HMI Software
  2. Do unzip the received file to the desktop of the windows device
  3. Open the folder “CanMan”
  4. Open the folder “Runtime”
  5. Double click the file “WinGRS”
  6. Now the software starts and you can use it to control the slitter

!Attention! The recipe from the unserviceable device are lost.

  1. Check the position of the switch!
  2. The internal battery is defect!

NOTE:
If you do not use the panel for a longer period (several weeks), the device should be turned off on the backside. Otherwise the internal battery will discharge and will get damaged!

 

NOTE:
The internal battery can be exchanged by opening the back cover of the unit. CM Article No. 009548

 

If you push the button on the right side, you are able to see the status of the integrated battery and optional available second battery.

 

The optional second battery is located at the back of the device.

 

Possible cause:

  • No supply of a slave on the bus system.
    • Check supply of all slaves.
      Emergency stop must be released.
  • Address of slave on Profibus is wrongly adjusted.
    • Check setting of all DIP switches on the lenze bus module and on the linmot controller.
      The correct setting you can find on the wiring diagram.
  • Wrong position of the switch for end resistant on the bus plug.
    • Check all switches on the complete bus system. Follow the cable seriously from PLC to last slave. First plug and plug of last slave must be set to ON, all other plugs to OFF.